GB50397-2007冶金电气设备工程安装验收规范(英文版)
上QQ阅读APP看本书,新人免费读10天
设备和账号都新为新人

3 Installation of High-Voltage Electrical Equipment

3.1 Dominant Items

3.1.1 The commissioning test of 3-500kV GIS,ACB,OCB,handcart type oil-minimum breaker,vacuum circuit breaker,disconnecting switch,etc.shall pass the commissioning test in accordance with the requirements of Article 2.1.5 of this code.

3.1.2 Grounding of bare and non-current carrying metal parts:all the flanges shall be connected across copper strips;the ground wires of both the base and support shall be connected securely;the crosssectional areas of both copper strips and branch lines shall be correctly selected and anticorrosion protection shall be provided without omission.